To upgrade to the i-Vu Pro v6.0 application
Custom Control Programs
• If you have custom logic created in EIKON that is being used as a part of the control sequence, you cannot
replace the custom control program with the automatically-generated one.
• Your EIKON-created control program will still run in an i-Vu Integrator that has been upgraded to run with the
i-Vu Pro v6.0 application.
• In order for a custom control program to support any of the new features available in the i-Vu Pro v6.0
application, it is necessary to apply an update to EIKON under the i-Vu Pro v3.1 application.
To apply the EIKON update:
1 Download the update file called
from the Service Intranet.
2 Open SiteBuilder v3.1.
3 Select
>
4 Browse to the location of the .update file and select it.
5 The screen should appear as seen below. Click
to apply the EIKON patch.
• You will need to use the EIKON program that was a part of your i-Vu Pro v3.1 system to edit any custom
control programs.
Custom programs created with EIKON will only run in an i-Vu Integrator. They are not supported in i-Vu
CCN Routers.
Local override
• Local overrides were not allowed in the i-Vu Pro v3.1 application.
• Control programs that are automatically generated during the discovery process in the i-Vu CCN Pro v4.2
application will support local overrides.
• To support new features in an EIKON-generated control program, you need to make some small changes.
○ v3.1 control programs typically had a section like the one shown in Figure 1. This took the current
schedule state and used a Carrier Schedule Write microblock to write it to a CCN device. This should be
replaced with logic similar to that shown in Figure 2.
i-Vu® Application Carrier Proprietary and Confidential CARRIER CORPORATION ©2014
Rev. 3/21/2014 All rights reserved